Cable gland reducer sizes

A reducer is ordered by thread pair, never by cable diameter. This page gives both thread diameters for the pairs that come up most often, so you can read the gap before you order — and covers the two situations where a reducer is the wrong answer entirely.

What it actually does

It changes the thread. The cable is a separate question.

A reducer is a short threaded sleeve, cut to the panel's existing thread on the outside and to the incoming gland's thread on the inside. Also sold as a thread adapter or a reducing bush. The size is written as that pair, in the order the threads meet: M32→M25 is an M32 outside with an M25 inside.

Two mismatches get confused constantly in enquiries. If the thread is wrong and the hole is already cut, a reducer solves it. If the cable falls outside the gland's clamping range, a reducer makes no difference at all — the seal is made by the insert compressing on the sheath, and the insert never sees the adapter. One is a thread problem, the other is a cable problem, and they arrive in the same email.

There is a third case that gets missed: when both the thread and the cable are wrong. A reducer plus a wider insert will close the thread and the gap, but it stacks two joints on one entry. At that point a larger gland and a re-cut hole is usually the cheaper answer over the life of the cabinet.

Three checks before the reducer goes on the order

  • Thread form, not diameter. M20 and PG13.5 are 0.4 mm apart and will not screw into each other. Confirm the form as well as the size.
  • Wall thickness. A reducer adds its own length. On a thin panel the inner thread can finish past the wall and leave the gland thread short.
  • Spanner clearance. The gland that goes in is now one size smaller, but it sits recessed inside the larger thread. A socket that fitted before may not reach it.

Send a photo of the entry next to a rule and we will read the thread form from it. For the family-by-family comparison — flank angles, designation styles and the conversion pairs that share a cable range — see the thread types and conversion pairs page.

Metric to metric

The five steps that cover most M-series enquiries.

Each row is one thread pair. The gap column is what the reducer body has to take up, which is also the reason a 40 mm hole cannot be bridged down to 16 mm in one part.

Existing threadThread ODGland threadThread ODGapTypical use
M40×1.540.0 mmM32×1.532.0 mm8.0 mmM32 glands into a 40 mm entry
M32×1.532.0 mmM25×1.525.0 mm7.0 mmM25 glands into a 32 mm entry
M25×1.525.0 mmM20×1.520.0 mm5.0 mmM20 glands into a 25 mm entry
M20×1.520.0 mmM16×1.516.0 mm4.0 mmM16 glands into a 20 mm entry
M16×1.516.0 mmM12×1.512.0 mm4.0 mmM12 glands into a 16 mm entry

Two steps down is the practical limit for a single reducer. Going from M40 to M20 in one part means 20 mm of wall in a sleeve that still has to hold a thread on both faces, and the sealing face gets thin enough to distort under torque. Order it as two reducers in series, or re-cut the hole.

PG and cross-thread

PG pairs, and the metric-to-PG conversions that are not reductions.

The first table is a true reduction: same thread family, smaller size. The second is a conversion between two different thread forms, where the diameters are close and the pitches are not.

Existing threadThread ODGland threadThread ODGap
PG2937.0 mmPG2128.3 mm8.7 mm
PG2128.3 mmPG1622.5 mm5.8 mm
PG1622.5 mmPG13.520.4 mm2.1 mm
PG13.520.4 mmPG1118.6 mm1.8 mm
PG1118.6 mmPG915.2 mm3.4 mm
Conversions

Metric hole, PG gland — and the other way round.

These look like the smallest gaps in the whole table and are the ones that come back as returns, because a 0.4 mm difference reads as “same size” on a cheap caliper.

Existing threadThread ODGland threadThread ODGap
M25×1.525.0 mmPG1622.5 mm2.5 mm
M20×1.520.0 mmPG13.520.4 mm0.4 mm
M20×1.520.0 mmPG1118.6 mm1.4 mm
PG1622.5 mmM20×1.520.0 mm2.5 mm
PG13.520.4 mmM20×1.520.0 mm0.4 mm

M20 is 20.0 mm at a 1.5 mm metric pitch. PG13.5 is 20.4 mm at an imperial pitch. The diameters overlap in the range a caliper reads, so diameter alone cannot tell them apart — confirm the pitch, or send a photo of the entry next to a rule.

Before you order

How to read the thread you already have.

A caliper across the outside of the thread is the starting point, not the answer. Four things decide which reducer you need, and only one of them is a diameter.

  • Measure the thread, not the hex. Across the flats is always the larger number and tells you nothing about the entry.
  • Half a millimetre decides it. M20 measures 20.0 mm and PG13.5 measures 20.4 mm. On a cheap caliper that is one reading apart, so confirm the pitch as well.
  • NPT tapers. The diameter changes along the thread, so measure at the first full thread and expect a smaller number at the end. A parallel reducer will not seal in it.
  • G is parallel but imperial. G ½″ measures about 21.0 mm, close enough to M20 to be mistaken for it in an enquiry.

Which problem do you actually have?

What is wrongCorrect partWill not fix it
Hole is M32, gland in hand is M25M32→M25 reducerA wider insert
Hole is M20, cable is 5 mm ODM20 body with a reducing insertA thread reducer
Hole is PG16, gland is M20PG16→M20 adapterForce — the pitches differ
Hole is M20, cable is 14 mmA larger entry, or a different routeAny insert or adapter

An insert reduces the cable. A reducer reduces the thread. They are not interchangeable.

The cost nobody puts on the drawing

A reducer makes the IP rating harder, not easier.

Every threaded face between the cable and the enclosure is a place the rating has to hold. A reducer adds one.

A gland straight into a panel has two sealing interfaces: the insert on the cable sheath, and the body face on the panel. Put a reducer in between and there is a third, between the reducer and the gland, plus a fourth where the reducer meets the panel. Each one is a torque value somebody has to get right on the line, and each one can work loose under vibration.

This is why an enclosure that holds IP66 with glands into the wall is not automatically IP66 with adapters in the same holes. The rating was demonstrated on the assembly that was tested. Change the assembly and the number belongs to a different assembly.

None of that makes reducers wrong. It makes them a repair, not a design. For a hole cut to the wrong size on an existing cabinet, a reducer with a sealing washer is the cheapest fix that keeps the cabinet in service. For a new build, cut the right hole.

Three ways the joint fails in service

  • Bottomed out. The reducer runs out of thread before its face touches the panel, so the washer never compresses. Happens on thick powder coat.
  • Undercut. Wall thickness plus reducer length leaves the gland thread short of the locknut, and the gland rocks under cable load.
  • Half a turn loose. Two threaded joints at the same torque do not behave like one. Vibration loosens the outer joint first.
Questions

Reducer questions before you order.

What reducer do I need for an M32 hole and an M25 gland?

An M32→M25 reducer: M32 thread on the outside to match the hole, M25 thread on the inside to take the gland. The size is always written outside first, because that is the thread the reducer has to match on the panel.

Can a PG gland go into an M20 hole?

Only with a conversion adapter, and the pair reads PG13.5 to M20 either way round. M20 measures 20.0 mm and PG13.5 measures 20.4 mm, so the diameters are close enough to look interchangeable and the thread forms are not. Metric is a 1.5 mm pitch; PG is an imperial pitch. Nothing seals between them without an adapter.

Does a reducer keep the IP rating?

The reducer does not carry an IP rating by itself — it adds a threaded joint that has to seal. A panel that was tested with a gland straight into the wall was not tested with a reducer in between. If the enclosure has to hold a stated IP figure, the assembly needs to be verified as built, not assumed from the parts list.

Is a reducer the same as a reducing insert?

No. A reducer changes the thread. A reducing insert changes the cable range inside one gland body. If the thread is wrong and the hole is already cut, you need a reducer. If the thread is right and the cable is too thin, you need an insert. Buying the wrong one is the most common mistake in this part of the order.

Can I use a reducer on an NPT entry?

Not with a parallel-thread reducer. NPT is tapered and seals on thread interference; metric and PG are parallel and seal on a face washer or an O-ring. A parallel reducer in a tapered hole bottoms out before it seals. For NPT entries, use an NPT-to-metric adapter made as a pair, or re-cut the hole.