Cable gland thread types, read off the part itself.

Four thread families cover almost every gland enquiry. This page tells them apart the way they get told apart on a real cabinet — by thread form and by what a caliper actually reads — and then matches the conversion pairs that share a cable range.

The four families

One table, four thread families.

Two things separate them: whether the thread is parallel or tapered, and which standard defines the form. Everything else on this page follows from those two.

FamilyWritten asThread formFlank angleSeals onStandard
Metric — MM20×1.5Parallel60°Face washer or O-ringISO metric screw thread
PG — PanzergewindePG13.5Parallel80°Face washerDIN 40430
NPT1/2″ NPTTapered60°On the thread flanks, with sealantASME B1.20.1
G — BSPPG 1/2Parallel55°Face washerISO 228-1

The designations carry their own warnings. An M20×1.5 writes its diameter and its pitch directly. A PG number is a code, not a diameter — PG13.5 is not 13.5 mm of anything. An NPT size is a nominal pipe designation, not the measured thread. G follows the same inch pattern as NPT, which is exactly why the two get swapped in enquiries.

Parallel threads seal on a face.

Metric, PG and G are all cut straight along their length. The joint is made where the gland body or the adapter face meets the panel, through a compressed washer or an O-ring. That means the seal lives or dies on the flat face, the gasket and the torque — not on the threads.

It also means a parallel gland has nothing to grab in a tapered hole. It screws in until it stops, the faces never meet, and the entry leaks on the first hose-down.

Tapered threads seal on the flanks.

NPT tightens on itself. The diameter shrinks along the thread, so the flanks wedge together as torque rises and the joint seals through interference, with sealant filling the spiral gap. No face washer is involved, and the panel entry has to be threaded to match, not drilled to a clearance size.

The taper is also the fastest way to identify an unknown thread by hand: one extra measurement along the length settles the biggest family question before any numbers are compared.

Identify by caliper

What a caliper reads, and the threads it cannot separate.

Measure across the outside of the male thread, not the hex, and match the reading below. The near-misses are listed deliberately, because those are the pairs that come back as returns.

Caliper readsCandidate threadsHow you decide
12.0 – 12.5 mmM12 / PG712.0 and 12.5 mm. Half a millimetre apart; the marking or the pitch decides.
15.2 mmPG9No metric thread sits here on a gland. PG9 reads 15.2 mm; M16 reads 16.0.
16.0 mmM16Clean metric read. PG9 at 15.2 is the nearest neighbor and a full size down.
18.0 – 18.6 mmM18 / PG1118.0 metric, 18.6 PG. Same trap as the 20 mm pair, one step smaller.
20.0 – 20.4 mmM20 / PG13.5The classic collision. 0.4 mm apart on a caliper that resolves 0.1; confirm before ordering.
21.0 – 21.3 mmG 1/2 / NPT 1/2″Parallel or tapered decides it. A tapered thread reads smaller toward the end.
22.0 – 22.5 mmM22 / PG160.5 mm apart, same pattern as the other metric–PG pairs.
26.4 – 26.7 mmG 3/4″ / NPT 3/4″Two inch families, 0.3 mm apart. Taper check first; the seal type is different too.
28.3 mmPG21Unmistakable once measured. No metric gland lands at 28.3.
32.0 – 33.4 mmM32 / G 1″ / NPT 1″A three-way collision. Taper check separates NPT; 32.0 vs 33.2 separates metric from G.
37.0 mmPG29PG29 reads 37.0; M40 is three millimetres above it.
47.0 – 47.8 mmPG36 / G 1 1/2″ / NPT 1 1/2″PG36 at 47.0, G at 47.8, NPT tapered. Measure twice along the thread.
59.3 – 60.3 mmPG48 / G 2″ / NPT 2″The big entries collide the same way the small ones do.

NPT diameters above are converted from the nominal outside diameters in the size chart (0.840 in for 1/2″, 1.050 in for 3/4″ and so on). The reading moves along a tapered thread, so take it at the first full thread and again near the end — a drop of more than a few tenths of a millimetre is the taper talking.

Three tie-breakers, in order.

  • Taper first. Two readings along the thread separate NPT from everything else before any diameter is compared.
  • The marking second. Most glands carry their designation on the body. M20×1.5 is self-describing; PG13.5 on a part rules out every metric guess at that diameter.
  • Cable range last. A shared range suggests which twins get confused, but never proves a thread. The seal is matched to the hole, not to the cable.

Why a photo beats a description

“It is about a 20 mil entry” has arrived here as M20, PG13.5 and G 1/2 on three different orders. A photo of the thread next to a rule, plus one reading, ends the conversation in one reply.

Send a photo of the entry
Conversion pairs

Conversions, matched by cable range.

These pairs are listed together because their clamping ranges overlap — which is the reason they get confused, and the reason a conversion adapter is chosen by cable first, then confirmed by thread.

PG threadCable rangeMetric twinIts rangeThread ODs
PG73 – 6.5 mmM123 – 6.5 mm12.5 vs 12.0 mm
PG94 – 8 mmM164 – 8 mm15.2 vs 16.0 mm
PG115 – 10 mmM185 – 10 mm18.6 vs 18.0 mm
PG13.56 – 12 mmM206 – 12 mm20.4 vs 20.0 mm
PG1610 – 14 mmM2210 – 14 mm22.5 vs 22.0 mm
PG2918 – 25 mmM4018 – 25 mm37.0 vs 40.0 mm
PG threadCable rangeInch twinIts rangeThread ODs
PG2113 – 18 mmNPT 3/4″13 – 18 mm28.3 vs 26.7 mm
PG2918 – 25 mmNPT 1″18 – 25 mm37.0 vs 33.4 mm
PG3622 – 32 mmNPT 1 1/4″22 – 32 mm47.0 vs 42.2 mm
PG4230 – 38 mmM5032 – 38 mm54.0 vs 50.0 mm
PG4834 – 44 mmM6337 – 44 mm59.3 vs 63.0 mm

Ranges that touch but do not overlap are listed too, marked honestly: PG42 starts where M50 starts plus two millimetres of cable, and PG48 reaches below where M63 begins. The pairing says “these two get mixed up in enquiries”, not “these two interchange”. They do not. A conversion adapter is the only part that bridges the families, and the reducer and adapter page lists both outside diameters and the gap for each pair.

The interchange question

Why none of them screw into each other.

Start with the flank angle. Metric and NPT cut a 60° profile; PG cuts 80°; G cuts 55°. Two threads with the same outside diameter but different angles touch on a sliver of flank, so the joint never reaches its rated torque. It feels tight by hand, then strips or rocks under a spanner.

Pitch does the same damage between metric and PG. The metric series runs on a stated pitch — 1.5 mm across most gland sizes — while PG follows its own pitch ladder. Over a few turns the mismatch accumulates into the interference that feels like “almost fits”, which is the most expensive phrase in this trade.

And the seal type follows the form. Parallel families seal on a face washer; NPT seals on its own flanks with sealant. Cross a parallel gland into a tapered hole and there is no sealing surface at all, whatever the diameters say.

The rule the workshop actually uses

If the threads do not match, the fix is a part cut for the pair — a thread adapter — not force, not a bigger gland, and not a hole re-cut on a cabinet that is already in service. Both ends of the adapter are written out explicitly, outside thread first.

See reducer and adapter sizes

An adapter adds a threaded joint, and every joint is somewhere the IP rating has to hold. It is a repair, not a design default.

Questions

Thread questions before you order.

What thread types do cable glands come in?

Four families cover almost every enquiry: metric (M20×1.5 and the M-series), PG (Panzergewinde, the legacy German standard), NPT (the North American tapered thread) and G or BSPP (parallel pipe thread to ISO 228). Metric dominates new IEC equipment, PG survives on European and imported machinery built to older drawings, NPT fills North American panels, and G shows up on process, marine and hydraulic-adjacent gear.

Are PG and metric cable gland threads interchangeable?

No. PG13.5 measures 20.4 mm and M20 measures 20.0 mm, so the diameters nearly overlap, but the thread forms are different standards — PG to DIN 40430, metric to the ISO series — with different pitches. They start by hand and cross-thread under a spanner. A thread adapter is the only clean way across, and the pair is written PG13.5→M20 either way round.

How do I identify an unknown cable gland thread?

Three checks, in order. Measure the outside of the thread with a caliper and match the reading against the table on this page. Run a finger or a second measurement along the thread: if the diameter shrinks, it is tapered and points to NPT. Then look for a marking — most glands carry the designation on the body. If the reading sits between two candidates, the taper check and the marking settle it.

Is G the same as NPT?

No, and they are the two that get swapped in enquiries because both are written in inches. G is a parallel thread to ISO 228 and seals on a face washer. NPT is tapered to ASME B1.20.1 and seals on the thread flanks with sealant. A G gland into an NPT hole, or the reverse, either bottoms out or leaks — the sealing method follows the thread form.

What is the most common cable gland thread?

For new equipment built to IEC practice, metric — M20 and M25 carry most panel and cabinet entries. North American equipment specifies NPT, and the sizes follow nominal pipe designations rather than a measured diameter. PG remains common enough on older European machinery that replacement enquiries still arrive daily.

Can I convert a PG hole to take a metric gland?

Yes, with a thread adapter, as long as the hole is not being re-drilled. The adapter is specified as PG thread outside to metric inside — for example PG16→M20 — and both diameters matter, because the pair is chosen by matching the cable range, not by force. The reducer and adapter page lists both outside diameters for each pair, and the gap the adapter has to take up.